Testimonials

MSHA Accident Report: November 23, 2020

  Houston Plant, Harris, TX – November 2020

MINE FATALITY- On November 23, 2020, a miner was electrocuted while troubleshooting a disconnect box for the classifier drive motor. The victim had the electrical disconnect box open and the main power supply was not deenergized.

“Best Practices” provided from MSHA:

  • Ensure electrical circuit components are properly designed and installed by qualified electrical personnel.

  • Ensure electrical troubleshooting and work are performed bypeople with proper electrical qualifications. Positively identify thecircuit on which work will be conducted.

  • Before performing electrical work, locate the visual disconnectaway from an enclosure and open it, lock it, and tag it, to ensureall electrical components in the enclosure are de-energized. Verify by testing for voltage using properly rated test equipment.

  • Wear properly rated and well maintained personal protective equipment, including arc flash protection such as a hood, gloves, shirt and pants.

  • Train miners on safe work practices for electrical equipment and circuits.

 

Click here for the full report from the United States Department of Labor

Leamington Greenhouse fined $120K after fatal workplace accident

Leamington Greenhouse fined $120K after fatal electrical shock

A Leamington greenhouse has been fined $120,000 after a worker died from an electrical shock in November 2018.
[Worker, 29 dies after being electrocuted – November 19, 2018]

Great Lakes Greenhouses Inc., a cucumber grower, pled guilty to failing to comply with a section of the Occupational Health and Safety Act in provincial court this week.

During the fatal incident, the worker was re-arranging wiring and doing breaker work when he received the shock.

The electricity had not been properly locked out as required by law, according to a news release form the ministry.

Along with the $120,000 fine, the company is also required to pay a 25 per cent victim fine surcharge, which goes to a fund to assist victims of crime.

 
For more information:
CTV News Windsor
CTV News Windsor- Article from NOV 2018
BlackburnNews
 
 

 

 

 

CAL/OSHA Investigating Fatal Electrocution

The city refused to identify the employee while withholding other details about the death, saying the workplace fatality was being investigated. The Sonoma County Coroner’s Office had not released the victim’s name as of Thursday night.

The city followed up with their own call to state regulators about the fatality shortly after paramedics and police arrived at the scene, she added.

Cal/OSHA was told that thee employee had been doing work on an energized subpanel at the site before electrocuted, Cal/OSHA spokesman Lucas Brown said.

Click here for the original news brief in The Press Democrat

 

MSHA Accident Report: July 9, 2020 Fatality

Hudson Sand Mine, Peach, Georgia – July 2020

The morning of July 9th, 2020, a mine superintendent with 36 years of mining experience lost his life when he contacted energized high-voltage components in a 4,160 volt (4,160 VAC), three-phase electrical enclosure.

The accident occurred because the mine operator’s policies, procedures, and training were inadequate to ensure that the employees properly de-energized, locked out, tagged, and tested the 4,160 VAC enclosure and internal components prior to performing work on the circuits.

Click here for the full investigation report 

 

“Best Practices” provided by MSHA: 
  • Follow these steps before performing electrical work inside a high voltage enclosure:
    1. Locate the high voltage visual disconnect away from the enclosure that supplies incoming electrical power to the enclosure.
    2. Open the visual disconnect to provide visual evidence that the incoming power cable(s) or conductors have been de-energized.
    3. Lock-out and tag-out the visual disconnect yourself. Never rely on others to do this for you.
    4. Ground the de-energized conductors.
  • Verify circuits are de-energized using properly rated electrical meters and non-contact voltage testers.
  • Ensure properly qualified miners perform all work on high voltage equipment.
  • Wear properly rated and well maintained personal protective equipment, including arc flash protection such as a hood, gloves, shirt and pants.
  • Train miners on safe work practices for high voltage electrical equipment and circuits.